AB-QM Pressure independent valve
AB-QM is a Pressure Independent Balancing and Control Valve, which limits the maximum flow, and at the same time function as a control valve operated by a several different types of Danfoss actuators.
AB-QM can be set to a precise design value and thereby provide full control over the real conditions in the system. The flow range of AB-QM series is 30-280.000 l/h.
|
|
|
Technische gegevens
| Artikelnr. | Type | Size | Description | Max. Flow |
AB-QM Pressure independent valve |
|
003Z0201
| AB-QM | DN10 | Without measuring nipples. | 275 l/h |
|
003Z0202
| AB-QM | DN15 | Without measuring nipples. | 450 l/h |
|
003Z0203
| AB-QM | DN20 | Without measuring nipples. | 900 l/h |
|
003Z0204
| AB-QM | DN25 | Without measuring nipples. | 1700 l/h |
|
003Z0205
| AB-QM | DN32 | Without measuring nipples. | 3200 l/h |
|
003Z0211
| AB-QM | DN10 | With measuring nipples. | 275 l/h |
|
003Z0212
| AB-QM | DN15 | With measuring nipples. | 450 l/h |
|
003Z0213
| AB-QM | DN20 | With measuring nipples. | 900 l/h |
|
003Z0214
| AB-QM | DN25 | With measuring nipples. | 1700 l/h |
|
003Z0215
| AB-QM | DN32 | With measuring nipples. | 3200 l/h |
|
003Z0251
| AB-QM | DN10 LF | Low flow version, without measuring nipples. | 150 l/h |
|
003Z0252
| AB-QM | DN15 LF | Low flow version, without measuring nipples. | 275 l/h |
|
003Z0261
| AB-QM | DN10 LF | Low flow version, with measuring nipples. | 150 l/h |
|
003Z0262
| AB-QM | DN15 LF | Low flow version, with measuring nipples. | 275 l/h |
|
003Z0705
| AB-QM | DN125 | With measuring nipples. | 90000 l/h |
|
003Z0706
| AB-QM | DN150 | With measuring nipples. | 145000 l/h |
|
003Z0707
| AB-QM | DN200 | With measuring nipples. | 190000 |
|
003Z0708
| AB-QM | DN250 | With measuring nipples. | 280000 |
|
003Z0715
| AB-QM | DN125 | High flow | 120000 l/h |
|
003Z0716
| AB-QM | DN150 | High flow | 229000 l/h |
|
003Z0717
| AB-QM | DN200 | High flow | 300000 l/h |
|
003Z0718
| AB-QM | DN250 | High flow | 442000 l/h |
|
003z0760
| AB-QM | DN40 | With 2 measuring PT points
Replaces 003Z0700 | 7500 l/h |
|
003z0761
| AB-QM | DN50 | With 2 measuring PT points
Replaces 003Z0710 | 12500 l/h |
|
003z0762
| AB-QM | DN50F | With 2 measuring PT points
Replaces 003Z0711 | 12500 l/h |
|
003z0763
| AB-QM | DN65 | With 2 measuring PT points
Replaces 003Z0702 | 20000 l/h |
|
003z0764
| AB-QM | DN80 | With 2 measuring PT points
Replaces 003Z0703 | 28000 l/h |
|
003z0765
| AB-QM | DN 100 | With 2 measuring PT points
Replaces 003Z0704 | 38000 l/h |
|
003Z1201
| AB-QM | DN10 | Without measuring nipples. | 275 l/h |
|
003Z1202
| AB-QM | DN15 | Without measuring nipples. | 450 l/h |
|
003Z1203
| AB-QM | DN20 | Without measuring nipples. | 900 l/h |
|
003Z1204
| AB-QM | DN25 | Without measuring nipples. | 1700 l/h |
|
003Z1205
| AB-QM | DN32 | Without measuring nipples. | 3200 l/h |
|
003Z1211
| AB-QM | DN10 | With measuring nipples | 275 l/h |
|
003Z1212
| AB-QM | DN15 | With measuring nipples | 450 l/h |
|
003Z1213
| AB-QM | DN20 | With measuring nipples | 900 l/h |
|
003Z1214
| AB-QM | DN25 | With measuring nipples | 1700 l/h |
|
003Z1215
| AB-QM | DN32 | With measuring nipples | 3200 l/h |
|
003Z1251
| AB-QM | DN10 LF | Low flow version, without measuring nipples. | 150 l/h |
|
003Z1252
| AB-QM | DN15 LF | Low flow version, without measuring nipples. | 275 l/h |
|
003Z1261
| AB-QM | DN10 LF | Low flow version, with measuring nipples. | 150 l/h |
|
003Z1262
| AB-QM | DN15 LF | Low flow version, with measuring nipples. | 275 l/h |
|
Documentatie
|
Data sheet
|
|
Instructie
AB-QM (DN 10-32) Setting tool - Gen.2011
VIBPG100_AB-QM setting tool.pdf
(0,8 Mb), Documentnr.: VIBPG100, Taal: Geen tekst, Datum van uitgave: 28/11 2011
|
AB-QM DN 10-32 (Gen.2011)
VIA7C13T_AB-QM_DN10-32.pdf
(4,8 Mb), Documentnr.: VIA7C13T, Taal: DK,GB,DE,ES,IT,SE,LT,EE,SI,CN,RO,HU,PL,RU, Datum van uitgave: 28/11 2011
|
AB-QM DN 125-250
VIC6C38Y_AB-QM_DN125-250.pdf
(2,4 Mb), Documentnr.: VIC6C38Y, Taal: DK,GB,DE,FR,ES,SE,NL,FI,LV,SI,CN,TR,HU,CZ,PL,RU, Datum van uitgave: 28/11 2011
|
AB-QM DN 40-100 (Gen. 2011)
VIA7E13T_AB-QM_DN40-100.pdf
(1,8 Mb), Documentnr.: VIA7E13T, Taal: DK,GB,DE,ES,IT,SE,LT,EE,SI,CN,RO,HU,PL,RU, Datum van uitgave: 28/11 2011
|
AB-QM handle (DN 125-150)
VIBPB100_AB-QM_HANDLE_DN125-150.pdf
(0,1 Mb), Documentnr.: VIBPB100, Taal: Geen tekst, Datum van uitgave: 10/12 2008
|
AB-QM handle (DN 125-150)
VIBPB200_AB-QM_HANDLE_DN125-250.pdf
(0,2 Mb), Documentnr.: VIBPB200, Taal: Geen tekst, Datum van uitgave: 28/11 2011
|
AB-QM handle (DN 40-100)
VIBPA300_AB-QM_handle_DN40-100.pdf
(0,1 Mb), Documentnr.: VIBPA300, Taal: Geen tekst, Datum van uitgave: 27/05 2009
|
AB-QM handle, DN 40-100 (gen.2011)
VIBPF100_AB-QM_handle_DN40-100_gen2011.pdf
(0,2 Mb), Documentnr.: VIBPF100, Taal: Geen tekst, Datum van uitgave: 28/11 2011
|
Adapter AB-QM/AME 13SU
VIBPC200_ADAPTER-AB-AME13SU.pdf
(0,2 Mb), Documentnr.: VIBPC200, Taal: Geen tekst, Datum van uitgave: 26/01 2010
|
Adapter for AB-QM (Gen. 2011)/AME 13 SU
VIBPE100_Adapter AB-QM gen.2011_AME 13SU.pdf
(0,3 Mb), Documentnr.: VIBPE100, Taal: Geen tekst, Datum van uitgave: 22/06 2011
|
AME 110 NL / AME 120 NL
VILEB35H_AME110NL-120NL.pdf
(3,0 Mb), Documentnr.: VILEB35H, Taal: DK,GB,DE,FR,ES,IT,SE,IS,NL,FI,LT,LV,EE,SK,HU,CZ,PL,RU, Datum van uitgave: 25/03 2010
|
AME 15QM
VILEA38C_AME 15QM.pdf
(2,0 Mb), Documentnr.: VILEA38C, Taal: DK,GB,DE,FR,ES,NL,FI,CN,PL,RU, Datum van uitgave: 12/11 2010
|
AME 55 QM
VICVB12N_AME 55QM.pdf
(1,2 Mb), Documentnr.: VICVB15H, Taal: DK,GB,DE,FR,ES,IT,SE,IS,NL,FI,LT,LV,EE,SK,HU,CZ,PL,RU, Datum van uitgave: 29/11 2010
|
Spare part - AB-QM DN 65-100 (old gen.)
VIC6E200_AB-QM_DN65-100.pdf
(0,6 Mb), Documentnr.: VIC6E200, Taal: Geen tekst, Datum van uitgave: 03/01 2012
|
Stroke limiter TWA-Z & AB-QM/AB-PM (Gen. 2011)
VIBPD200_AB-QM stroke limiter gen.2011.pdf
(0,5 Mb), Documentnr.: VIBPD200, Taal: Geen tekst, Datum van uitgave: 10/05 2012
|
|
|
Gerelateerde producten
|
AME QM push-pull actuators for large AB-QM
|
The AME QM actuators are used with the AB-QM pressure independent balancing and control valve. DN40 to DN100: AME 15 QM
DN125 and DN150: AME 55 QM
DN200 and DN250: AME 85 QM
The actuators automatically adapt the stroke to the valve end positions which reduces commissioning time. They are very flexible actuators, which can be controlled by all types of control signals like voltage, current and 3-point.
|
|
AMI 140 + AME/V 110/120 NL
|
AMV(E) 110 NL and AMV(E) 120 NL actuators are used 0-10V and 3-point gear actuators that combine with AB-QM (sizes DN10-DN32) for superb control.
AMI 140 is 2-point 3-wire actuator used with AB-QM DN10-DN32
|
|
TWA-Z Actuators
|
Thermal actuator for Danfoss automatic flow limiter type AB-QM and for valve type VZL.
|
|
|
|
|
|